Sizing Filters for High-Pressure Gas — Why 1000 Nm³/h at 200 bar Is Only About 4 m³/h
Flows for natural gas, CNG and hydrogen are specified in Nm³/h or Sm³/h. A filter, however, sees the actual volume flow at operating pressure and temperature. At 200 bar this is a few hundred times smaller — 1000 Nm³/h of methane is only about 4 m³/h. Getting this conversion right avoids oversized housings and wrong pressure-drop expectations.
Reconnaître les symptômes
- A filter selected from a standard-flow table looks far too large for the pipe size
- Supplier proposals for the same duty differ widely in housing size
- Pressure-drop values in data sheets do not match what is measured in the plant
- Uncertainty whether a flow is stated in Nm³/h (0 °C) or Sm³/h (15 °C)
- Flow at the dispenser or point of use is sized like the station capacity
Causes
Standard flow used instead of actual flow
Nm³/h refers to 1.013 bar and 0 °C; the filter sees the compressed volume
Ideal-gas assumption at high pressure
at 200 bar methane is noticeably more compressible than an ideal gas (Z ≈ 0.76–0.84 between 0 and 30 °C), so the actual flow is lower than the ideal-gas estimate
Reference conditions mixed up
Sm³ (15 °C) and Nm³ (0 °C) differ by about 5 %
Temperature ignored
warmer gas has a larger actual volume (at 200 bar: about 3.8 m³/h at 0 °C, 4.3 m³/h at 15 °C, 4.7 m³/h at 30 °C per 1000 Nm³/h methane)
Pressure drop rated for air
the dynamic viscosity of methane at 200 bar is close to that of air, but density is much higher; clean ΔP data should be checked for the real gas and actual flow
Liste de contrôle diagnostic
- 1State the flow with its reference conditions: Nm³/h (0 °C, 1.013 bar) or Sm³/h (15 °C)
- 2Give the operating pressure in bar g and the gas temperature at the filter
- 3Convert with the real-gas equation: Q_actual = Q_N × (p_N / p) × (T / T_N) × Z
- 4Example: 1000 Nm³/h methane at 200 bar g and 15 °C → about 4.3 m³/h actual (Z ≈ 0.8); natural gas is about 3 % lower
- 5Choose the connection size by the pipework (e.g. DN25 / 1″ NPT), then check the element pressure drop at the actual flow
- 6Define the change criterion (e.g. 0.7 bar ΔP) and leave reserve for element loading
Trouver le filtre approprié pour ce problème
Saisissez vos données de fonctionnement — nos outils vous guident vers l'élément et le corps appropriés. Ou envoyez-nous vos données pour une recommandation sur mesure.
Recherche d'élément
RecommandéL'élément filtrant approprié pour votre fluide et votre application en moins de 60 secondes — point de départ recommandé.
Trouver l'élémentUtiliser la sélection de corps
Choisir le corps approprié — matériau, classe de pression, raccords et purge.
Sélectionner le corpsDemander un conseil
Vous préférez un contact personnel ? Envoyez vos données de fonctionnement et nous recommandons la configuration appropriée.
Envoyer une demandeDécrivez votre situation — nous trouvons la solution appropriée
Chaque problème de filtration a des causes spécifiques qui nécessitent des solutions spécifiques. Envoyez-nous vos conditions de fonctionnement et nous établirons une recommandation sur mesure.